FRONIUS PRIMO 10kW
FRONIUS PRIMO 10.0 - 208-240
Grid Tied Fronius Transformerless Inverter 10000 watts
Click to download datasheets: https://documentcloud.adobe.com/link/track?uri=urn:aaid:scds:US:4bdc9645-7e05-3470-8840-063ac1d5e749
Model No.: FRONIUS PRIMO 10.0 - 208-240
The transformerless Fronius Primo is the ideal compact single-phase inverter for residential and small-scale commercial applications with power categories from 3.8 to 8.2 kW. In accordance with ESA rules for residential applications, the Fronius Primo can operate efficiently at a maximum input voltage of 600 V. And for increased efficiency and additional cost savings for commercial applications, the Fronius Primo can operate at the maximum input voltage of 1,000 V. Industry leading features now come standard with the Fronius Primo, including dual maximum power point tracking, arc fault protection, integrated wireless monitoring and SunSpec Modbus interfaces for seamless monitoring and datalogging via Fronius’ online and mobile platform, Fronius Solar.web.
TECHNICAL DATA FRONIUS PRIMO:
- Dimensions (width x height x depth): 20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 20.6 cm
- Weight: 82.5 lbs. / 37.4 kg
- Degree of protection: NEMA 4X
- Night time consumption: < 1 W
- Inverter topology: Transformerless
- Cooling: Controlled forced ventilation, variable speed fan
- Installation: Indoor and outdoor installation
- Ambient operating temperature range: -40 to 140 F / -40 to 60 C
- Permitted humidity: 0 - 100 %
- DC connection terminals: 4x DC+1, 2x DC+2 and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
- AC connection terminals: Screw terminals 12 - 6 AWG
- Revenue Grade Metering: Optional (ANSI C12.1 accuracy)
- Certificates and compliance with standards: UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC Article 690-2014, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
- PROTECTIVE DEVICES: STANDARD WITH ALL PRIMO MODELS
- AFCI: Yes
- Ground Fault Protection with Isolation Monitor Interrupter: Yes
- DC disconnect: Yes
- DC reverse polarity protection: Yes
INTERFACES - AVAILABLE WITH ALL FRONIUS PRIMO MODELS
Standard - USB (A socket) | Datalogging and inverter update via USB
Standard - 2x RS422 (RJ45 socket) | Fronius Solar Net, interface protocol
Optional - 6 inputs or 4 digital inputs/outputs | External relay controls
Optional - Wi-Fi*/Ethernet/Serial/Datalogger and webserver | Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU
Please click on datasheet for technical specifications.